GCS Low Voltage Withdrawable Switch Cabinet

GCS Low Voltage Withdrawable Switch Cabinet
GCS Low Voltage Withdrawable Switch Cabinet

GCS Low Voltage Withdrawable Switch Cabinet

GCS-type low-voltage withdrawable switchgear is suitable for use in low-voltage distribution systems such as power plants, substations, petrochemical sectors, factories and mines, high-rise buildings, and so on, as well as for electric energy conversion, distribution, and control such as capacitance compensation.

The GCS type low-voltage withdrawable switchgear has high making and breaking capabilities, good dynamic and thermal stability, an advanced and reasonable structure, a flexible electrical scheme, a high protection level, safety and reliability, ease of maintenance, and excellent technical performance indicators.

GCS-type low voltage withdrawable switchgear is engineered for heavy distribution duty — power plants, substations, petrochemical sites, factories, mines, and high-rise buildings — combining feeder distribution, motor control, and capacitor compensation sections in one drawer-based line-up. High making and breaking capability together with strong dynamic and thermal stability keeps these boards composed where fault levels and load continuity both run high.

Every GCS line-up we deliver starts from your single-line diagram and discrimination study: drawer assignments, busbar sizing, and protection settings are locked before fabrication begins. Since 2010 our teams have completed more than 4,000 industrial projects, and CNC fabrication plus in-house wiring keeps multi-cabinet GCS rows consistent in fit, finish, and testing.

Feature of Low Voltage Withdrawable Switch Cabinet

  1. The cabinet frame uses double-folding technology with aluminum-zinc-coated steel plates. The frame has modular holes spaced at 25mm intervals (K profile). The frame is simple to construct and durable. The entire frame is joined exactly by transverse and longitudinal bolts, and the frame structure requires no maintenance.

  2. The shell is electroplated and powder coated. The top cover of the horizontal busbar region may be removed for easier on-site busbar installation.

  3. Each functional room is clearly segregated, with divisions primarily divided into functional unit rooms and cable rooms. Each unit's functions are autonomous and have no effect on one another.

  4. The horizontal busbar is mounted flat beneath the cabinet, increasing its capacity to withstand the electric power generated by a short-circuit current.

  5. It features a drawer-style construction and can accommodate up to 36 circuits. The rated current of the circuit is 400A or less. The drawer circuit may be converted to three positions without compromising its protection level.

  6. Each unit may accommodate up to 11 drawers or 22 1/2 drawers.

  7. The drawer has five positions: opening, shutting, testing, pulling out, and isolating, and it features clear signals that correspond to sound, light, and text directions.

GCS Low Voltage Withdrawable Switch Cabinet Technical Parameters

Rated insulation voltage Uiexchange690V、1000V
Rated operating voltage UeMain circuit/
auxiliary circuit
exchange400V、660V
exchange380V、200V
Direct current200V、100V
Rated impulse withstand voltage Uimp8KVVertical busbar rated current1000V
Overvoltage levelRated peak withstand current (0.1S) IPKVertical 105kA
pollution level3 Level 176kA
Rated frequency50(60)HzRated peak withstand current (0.1S) IPKVertical 80kA
Horizontal bus rated currentIe≤4000A Level 80kA
Enclosure ratingIP30、IP40Dimensions2200x(400,600,800,1000)x(600,800,1000)

Key Specifications & Options

The configuration below reflects the options we build to order for GCS low voltage withdrawable switch cabinets. Every parameter can be adjusted to match your drawings and site conditions — send us your requirements and our engineers will confirm what applies to your project.

ParameterOptions / Typical Range
Assembly typeWithdrawable low voltage switchgear (GCS type) for distribution and motor control
Rated voltageAC 50 Hz, 380/400 V working voltage on a 660 V insulation class
Functional unitsDrawer-type outgoing units, with fixed feeder and compensation compartments as required
Main busbar currentEngineered to the load schedule and fault level of the line-up
Electrical performanceHigh making and breaking capability with verified dynamic and thermal stability
Protection degreeIP30 typical for the assembled board
Applicable standardsGB 7251 series for LV assemblies, corresponding to IEC 61439
Typical applicationsPower plant station service, substation LV boards, petrochemical plants, high-rise buildings

Frequently Asked Questions

How does GCS differ from GCK and MNS?

All three are withdrawable national-standard families, and the differences live in drawer formats, busbar arrangement, and frame details — which in practice means each fits different existing fleets and spare-part stocks. We select per your drawings and maintenance policy rather than by preference, and confirm dimensions and interfaces in the quotation.

Withdrawable or fixed construction — what changes for maintenance?

Withdrawable GCS sections let a single drawer be isolated, tested, and exchanged while its section stays in service; fixed boards are simpler and cheaper but need the circuit shut down to work on it. Where continuity pays for itself — process plants, towers — withdrawable is standard practice.

Can a GCS line-up include capacitor compensation?

Yes — compensation cabinets sit in the row and couple to the main busbars, with automatic step control following the plant power factor. This is common where the utility contract penalizes low power factor and the transformer headroom matters.

Which standards apply to GCS boards?

The GB 7251 series for low voltage assemblies, corresponding to IEC 61439. Design verification — strength, temperature rise, short-circuit withstand — follows the series, and we deliver the documentation with the completed board.